GE Consumer & Industrial
Multilin
LISTED
52TL
IND.CONT. EQ.
E83849
239
MOTOR PROTECTION RELAY
Communications Guide
Firmware Revision: 2.7x
239PC Software: 2.7x or newer
Manual P/N: 1601-9031-A1 (GEK-113398)
Copyright © 2007 GE Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
*1601-0067-DC*
TRIP
ALARM
AUXILIARY
SERVICE
PICKUP
COMMUNICATE
RESET
STORE
ACTUAL
VALUE
MESSAGE
SETPOINT
239 Motor Protection Relay
CAUSE OF LAST TRIP:
MECHANICAL JAM
ISO9001:2000
G
E
M
U
L
T
I
L
I
N
R
E
G
I
S
T
E
R
E
D
GE Multilin’s Quality
Management System is
registered to ISO9001:2000
QMI # 005094
UL # A3775
Vedere la pagina 0
1 2 3 4 5 6 ... 57 58

Sommario

Pagina 1 - *1601-0067-DC*

GE Consumer & IndustrialMultilinLISTED52TLIND.CONT. EQ.E83849239MOTOR PROTECTION RELAYCommunications GuideFirmware Revision: 2.7x239PC Software: 2

Pagina 2

CG–6 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDECG.3 239 Supported Modbus FunctionsThe following functions are supported b

Pagina 3 - Table of Contents

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–7FUNCTION CODE - 1 byte 03 read registersBYTE COUNT - 1 byte 06 3 registers

Pagina 4 - TABLE OF CONTENTS

CG–8 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEThis command allows the master to store a single setpoint into the memory

Pagina 5 - 239 Motor Protection Relay

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–9MESSAGE FORMAT AND EXAMPLERequest status from slave 11.Master Transmission

Pagina 6

CG–10 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEMESSAGE FORMAT AND EXAMPLELoopback test from slave 11.Master Transmission

Pagina 7 - CG.2 Data Packet Format

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–11DATA 1 - 2 bytes 00 96 data for address 1028DATA 2 - 2 bytes 00 96 data f

Pagina 8

CG–12 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDECG.4 16: Performing CommandsSome PLCs may not support execution of comman

Pagina 9 - CG.2.2 Timing

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–13CG.5 Error ResponsesWhen a 239 detects an error other than a CRC error, a

Pagina 10 - MESSAGE FORMAT AND EXAMPLE

CG–14 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDECG.6 Memory Map InformationThe data stored in the 239 is grouped as Setpo

Pagina 11 - CG.3.2 05: Execute Operation

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–15CG.6.2 239 Memory MapTable CG–1: 239 Memory Map (Sheet 1 of 21)REG ADDR (

Pagina 12 - CG.3.4 07: Read Device Status

© 2007 GE Multilin Incorporated. All rights reserved.GE Multilin 239 Motor Protection Relay Communications Guide for revision 2.7x.239 Motor Protectio

Pagina 13 - CG.3.5 08: Loopback Test

CG–16 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE002F Reserved0030 Calibration Day --- --- --- F1 day of calibration0031 C

Pagina 14

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–170090 Reserved↓↓00FF ReservedUser Definable Register (Input Registers) A

Pagina 15 - COMMUNICATIONS GUIDE

CG–18 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE0188 Register address for User Definable Data 0008† 1 --- F1 00189 Regist

Pagina 16 - CG.4 16: Performing Commands

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–190216 Pre-Trip RTD 1 Temp. (RTD Option)--- --- °C F2**** N/A0217 Pre-Trip

Pagina 17 - CG.5 Error Responses

CG–20 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE0233 Reserved0234 Reserved0235 Reserved0236 Reserved0237 Reserved023

Pagina 18 - CG.6 Memory Map Information

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–210250 DEBUG ADC Reference --- --- --- F1 N/A0251 DATA Thermistor Reading -

Pagina 19 - CG.6.2 239 Memory Map

CG–22 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE026C Message Buffer characters 25 and 26--- --- ASCII F8 N/A026D Message

Pagina 20 - COMMUNICATIONS GUIDE

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–23Setpoint Values (Holding Registers) Addresses – 1000 to 11EF1000 PREFEREN

Pagina 21

CG–24 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE101E Reserved101F Reserved1020 CTINPUTSPhase CT Primary 0-1500 5 A F1 *

Pagina 22

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–25103E Reserved103F Reserved1040 ALARMRELAYAlarm Operation 0-1 1 --- F16

Pagina 23

TABLE OF CONTENTS239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE TOC–ITable of ContentsCOMMUNICATIONS ...

Pagina 24

CG–26 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE105D Reserved105E Reserved105F Reserved1060 IMMEDIATEOVERLOADImmediate

Pagina 25

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–27107D Reserved107E Reserved107F Reserved1080 HOT MOTOR % Thermal Capaci

Pagina 26

CG–28 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE109A Thermistor Cold Resistance 1-300 1 0.1 kΩ F1 3 = 0.3 kΩ109B Thermist

Pagina 27

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–2910B8 RTD SENSOR RTD Sensor Fail Alarm (RTD Option)0-1 1 --- F20 0 = OFF10

Pagina 28

CG–30 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE10D8 ANALOGSIMULATION Simulation (AN Option) 0-1 1 --- F20 0 = OFF10D9 Fo

Pagina 29

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–3110F8 FLASHMESSAGEFlash message characters 1 and 232-127 1 ASCII F8 "

Pagina 30

CG–32 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE1110 PROGRAMMA-BLEMESSAGEProgrammable message characters 1 & 232-127

Pagina 31

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–331128 SWITCHSIMULATIONSimulation 0-1 1 --- F20 0 = OFF1129 Emergency Resta

Pagina 32

CG–34 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE1190 OPTIONSWITCH 1Option Switch 1 characters 1 and 232-127 1 ASCII F8 &

Pagina 33

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–3511B6 Option Switch 2 characters 13 and 1432-127 1 ASCII F8 "H "

Pagina 34

TOC–II 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDETABLE OF CONTENTS

Pagina 35

CG–36 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEMEMORY MAP TABLE NOTESNotes: * = Minimum Setpoint value represents “OFF”

Pagina 36

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–37 0 = No Trip --- 1 = Overload --- 2 = Short Circuit --- 3 = Mechanical Ja

Pagina 37

CG–38 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE 0 = No Trip --- 1 = Overload --- 2 = Short Circuit --- 3 = Mechanical Ja

Pagina 38

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–39 FB02 = VALUE DOWN ---F8 TWO ASCII CHARACTERS FFFF 32-127 = ASCII Charact

Pagina 39

CG–40 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEF14 UNSIGNED INTEGER - YES / NO FFFF 0 = No --- 1 = Yes ---F15 UNSIGNED I

Pagina 40 - MEMORY MAP TABLE NOTES

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–41 0 = Off --- 1 = Alarm --- 2 = Auxiliary --- 3 = Trip --- 4 = Alarm &

Pagina 41 - CODE DESCRIPTION BITMASK

CG–42 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE 4 = Alternate Setpoints --- 5 = Disable Starts ---F27 COMMAND FFFF 1 = R

Pagina 42

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–43 0 = Normal --- 1 = Trip --- 2 = Alarm --- 3 = Trip and Alarm --- 4 = Rel

Pagina 43

CG–44 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEF36 SIMULATED SWITCH STATE FFFF 0 = OPEN --- 1 = CLOSED ---F38 GROUND TRI

Pagina 44

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–45F45 UNSIGNED LONG INTEGER(NUMERICAL DATA)FFFFFFFFF100 SWITCH INPUT STATUS

Pagina 45

239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–1239 Motor Protection RelayCommunications GuideGE Consumer & IndustrialMultilinTRIPALARMAUXIL

Pagina 46

CG–46 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE Not Used 0200 Not Used 0400 Not Used 0800 Not Used 1000 Not Used 2000 No

Pagina 47

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–47 Short Circuit 0020 Stator RTD (RTD Option) 0040 Bearing RTD (RTD Option)

Pagina 48

CG–48 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEF105 INTERNAL FAULT ERROR CODE FFFF ADC Reference Out of Range 0001 HC705

Pagina 49

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–49 Not Used 0800 Not Used 1000 Not Used 2000 Not Used 4000 Not Used 8000F10

Pagina 50

CG–50 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE Communicate 0020 Not Used 0040 Not Used 0080 Not Used 0100 Not Used 0200

Pagina 51

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–51 2 = 3rd Group --- 3 = 4th Group ---F114 Ground Current Scale Factor FFFF

Pagina 52

CG–52 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE

Pagina 53

INDEX 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG-INDEX–1IndexIndexABCCOMMUNICATIONSdata format ...

Pagina 54

CG-INDEX–2 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDEINDEXfunction code 08 – loopback test ...

Pagina 55

CG–2 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEis important in RS485 communications. Each '+' terminal of every

Pagina 56

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–3CG.2 Data Packet FormatA complete request/response sequence consists of th

Pagina 57

CG–4 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEnumber. This number is first shifted left 16 bits and then divided by a ch

Pagina 58

COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–58. is j = 8? No: go to 5.Yes: go to 9.9. i+1 --> i10. is i = N? No: go